SPEAKER: So today, we set aside
that part and look at what

00:00:23.300 --> 00:00:28.310 align:middle line:84%
is often the hardest thing
to actually make it real,

00:00:28.310 --> 00:00:32.880 align:middle line:84%
to put in the ground, design,
build, learn, research.

00:00:32.880 --> 00:00:35.120 align:middle line:90%
So we get to work in a sense.

00:00:35.120 --> 00:00:40.530 align:middle line:84%
And just like yesterday, there
are many people, experts,

00:00:40.530 --> 00:00:45.080 align:middle line:84%
ideas that we couldn't ram
into this two day session

00:00:45.080 --> 00:00:46.830 align:middle line:90%
in 10-minute segments.

00:00:46.830 --> 00:00:49.290 align:middle line:90%
And so we are so aware of that.

00:00:49.290 --> 00:00:52.070 align:middle line:90%
There is still a whiteboard.

00:00:52.070 --> 00:00:54.950 align:middle line:84%
At the break, you
can add the names

00:00:54.950 --> 00:00:57.500 align:middle line:84%
of people and experts
and ideas that you really

00:00:57.500 --> 00:00:58.860 align:middle line:90%
think need to be in here.

00:00:58.860 --> 00:01:01.990 align:middle line:84%
We may have attempted
to get them here,

00:01:01.990 --> 00:01:06.190 align:middle line:84%
but we really want to hear that
from you as well as feedback.

00:01:06.190 --> 00:01:08.830 align:middle line:84%
We're trying to
capture and share

00:01:08.830 --> 00:01:11.680 align:middle line:84%
a pulse of information,
the state of knowledge.

00:01:11.680 --> 00:01:14.960 align:middle line:84%
As you saw yesterday,
there's all kinds of views,

00:01:14.960 --> 00:01:17.570 align:middle line:84%
all kinds of perspectives, all
kinds of voices and language,

00:01:17.570 --> 00:01:19.460 align:middle line:90%
and we just welcome them all.

00:01:19.460 --> 00:01:22.270 align:middle line:84%
We're not saying
that we shouldn't

00:01:22.270 --> 00:01:25.120 align:middle line:90%
have some healthy debates.

00:01:25.120 --> 00:01:28.310 align:middle line:84%
So I really hope it
goes as well today.

00:01:28.310 --> 00:01:33.040 align:middle line:84%
And I want to pass it over to
Juliet, who will be moderating

00:01:33.040 --> 00:01:35.247 align:middle line:90%
our very first session.

00:01:35.247 --> 00:01:35.830 align:middle line:90%
AUDIENCE: Yay!

00:01:35.830 --> 00:01:40.253 align:middle line:90%
[APPLAUSE]

00:01:40.253 --> 00:01:42.100 align:middle line:90%


00:01:42.100 --> 00:01:43.503 align:middle line:90%
JULIET: Hello, everyone!

00:01:43.503 --> 00:01:44.920 align:middle line:84%
We're excited to
start our day off

00:01:44.920 --> 00:01:48.580 align:middle line:84%
with some talks about design
principles for geothermal energy

00:01:48.580 --> 00:01:49.190 align:middle line:90%
networks.

00:01:49.190 --> 00:01:52.060 align:middle line:84%
We have three great speakers,
two of them in person

00:01:52.060 --> 00:01:53.360 align:middle line:90%
and then one online.

00:01:53.360 --> 00:01:56.950 align:middle line:84%
So we'll start our day
with Connor Dacquay, who

00:01:56.950 --> 00:01:59.140 align:middle line:84%
is a licensed
engineer at GeoFease

00:01:59.140 --> 00:02:03.445 align:middle line:84%
and who teaches in IGSHPA
ground-source heat pump course.

00:02:03.445 --> 00:02:03.945 align:middle line:90%
Connor?

00:02:03.945 --> 00:02:15.750 align:middle line:90%


00:02:15.750 --> 00:02:19.650 align:middle line:84%
CONNOR DACQUAY: OK,
good morning, everyone.

00:02:19.650 --> 00:02:22.380 align:middle line:84%
So I spoke with Zainab
before this meeting.

00:02:22.380 --> 00:02:25.170 align:middle line:84%
And I just wanted
to thank all of HEET

00:02:25.170 --> 00:02:26.350 align:middle line:90%
for putting on this session.

00:02:26.350 --> 00:02:28.320 align:middle line:84%
I left yesterday
quite optimistic

00:02:28.320 --> 00:02:32.370 align:middle line:84%
on the geothermal district space
in the United States, which is--

00:02:32.370 --> 00:02:36.070 align:middle line:84%
it's very relieving,
I'll say, with the times.

00:02:36.070 --> 00:02:38.260 align:middle line:84%
So thank you all
for putting this on.

00:02:38.260 --> 00:02:41.820 align:middle line:84%
So my background
is in engineering.

00:02:41.820 --> 00:02:44.610 align:middle line:84%
I have a doctorate in what's
called Earth energy resource

00:02:44.610 --> 00:02:45.600 align:middle line:90%
engineering.

00:02:45.600 --> 00:02:48.450 align:middle line:84%
I'm a licensed engineer
in the state of New York

00:02:48.450 --> 00:02:51.930 align:middle line:84%
and also the province
of Ontario and Canada.

00:02:51.930 --> 00:02:55.687 align:middle line:84%
I also help teach the certified
geoexchange designer course,

00:02:55.687 --> 00:02:58.020 align:middle line:84%
which is run by IGSHPA,
International Ground Source Heat

00:02:58.020 --> 00:02:58.980 align:middle line:90%
Pump Association.

00:02:58.980 --> 00:03:01.520 align:middle line:84%
And this specific
slide deck today

00:03:01.520 --> 00:03:05.360 align:middle line:84%
just goes through that
introductory level,

00:03:05.360 --> 00:03:07.200 align:middle line:90%
CGD-type course.

00:03:07.200 --> 00:03:09.500 align:middle line:84%
So we thought we'd start
with the fundamentals of heat

00:03:09.500 --> 00:03:12.830 align:middle line:84%
transfer to get into the
ground-source heat pumps

00:03:12.830 --> 00:03:13.740 align:middle line:90%
and how they work.

00:03:13.740 --> 00:03:17.210 align:middle line:84%
So we have conduction,
convection, and radiation.

00:03:17.210 --> 00:03:20.690 align:middle line:84%
By definition, conduction
is when heat is directly

00:03:20.690 --> 00:03:22.700 align:middle line:84%
transmitted through a
substance when there

00:03:22.700 --> 00:03:24.360 align:middle line:90%
is a difference in temperature.

00:03:24.360 --> 00:03:25.820 align:middle line:84%
So if you're
holding a metal rod,

00:03:25.820 --> 00:03:27.810 align:middle line:84%
and that metal rod
heats up on one end,

00:03:27.810 --> 00:03:29.540 align:middle line:84%
you feel that heat
through your hand

00:03:29.540 --> 00:03:32.030 align:middle line:84%
through conduction
of that metal rod.

00:03:32.030 --> 00:03:35.480 align:middle line:84%
We have convection, which is
the rising motion of warmer

00:03:35.480 --> 00:03:38.930 align:middle line:84%
areas of a liquid or gas, and
the sinking motion of cooler

00:03:38.930 --> 00:03:40.860 align:middle line:90%
areas of liquid or gas.

00:03:40.860 --> 00:03:43.603 align:middle line:84%
So if you're holding your
hand over a fire, that heat,

00:03:43.603 --> 00:03:45.270 align:middle line:84%
you're not physically
touching anything,

00:03:45.270 --> 00:03:48.380 align:middle line:84%
but you feel that heat,
and that's convection.

00:03:48.380 --> 00:03:50.360 align:middle line:84%
Lastly, we have
radiation, the process

00:03:50.360 --> 00:03:52.520 align:middle line:84%
where heat energy is
transferred from one

00:03:52.520 --> 00:03:54.200 align:middle line:84%
object to another
through the emission

00:03:54.200 --> 00:03:55.530 align:middle line:90%
of electromagnetic waves.

00:03:55.530 --> 00:03:58.837 align:middle line:84%
I promise the rest of this
presentation won't be this dry.

00:03:58.837 --> 00:04:00.420 align:middle line:84%
Just getting through
the fundamentals.

00:04:00.420 --> 00:04:02.270 align:middle line:84%
But when your
sun-tanning, you feel

00:04:02.270 --> 00:04:05.060 align:middle line:90%
that heat, that's radiation.

00:04:05.060 --> 00:04:06.500 align:middle line:90%
So geothermal.

00:04:06.500 --> 00:04:07.440 align:middle line:90%
What is geothermal?

00:04:07.440 --> 00:04:10.760 align:middle line:84%
Well, "geo" means relating
to the Earth, and "thermal"

00:04:10.760 --> 00:04:12.090 align:middle line:90%
means relating to heat.

00:04:12.090 --> 00:04:14.150 align:middle line:84%
So the Earth temperature
is relatively

00:04:14.150 --> 00:04:16.040 align:middle line:90%
constant throughout the year.

00:04:16.040 --> 00:04:17.339 align:middle line:90%
It's around 50 here.

00:04:17.339 --> 00:04:19.260 align:middle line:84%
I think it's 55
degrees Fahrenheit.

00:04:19.260 --> 00:04:21.720 align:middle line:84%
Whereas in the winter time,
it's 10 degrees outside.

00:04:21.720 --> 00:04:24.930 align:middle line:84%
And then in the summertime,
around 90 degrees outside.

00:04:24.930 --> 00:04:28.410 align:middle line:84%
But the ground stays that same
50, 55 degrees Fahrenheit.

00:04:28.410 --> 00:04:32.210 align:middle line:84%
And to harness that energy,
you can install a ground heat

00:04:32.210 --> 00:04:35.550 align:middle line:84%
exchanger, which is plastic pipe
that's buried in the ground.

00:04:35.550 --> 00:04:40.220 align:middle line:84%
And it transfers heat to a
volume of Earth around that pipe

00:04:40.220 --> 00:04:42.020 align:middle line:90%
through various ways.

00:04:42.020 --> 00:04:44.030 align:middle line:84%
Shallow ground heat
exchangers take

00:04:44.030 --> 00:04:46.730 align:middle line:84%
advantage of radiation,
mainly conduction,

00:04:46.730 --> 00:04:50.340 align:middle line:84%
but there's also convective heat
transfer with that ground water.

00:04:50.340 --> 00:04:54.200 align:middle line:84%
You have heat exchange fluid
that's pumped through the pipe.

00:04:54.200 --> 00:04:56.130 align:middle line:84%
I'm getting used
to this laser here.

00:04:56.130 --> 00:04:59.070 align:middle line:84%
Heat exchange fluid that's
pumped through this pipe

00:04:59.070 --> 00:05:01.360 align:middle line:84%
and then connected
to that heat pump.

00:05:01.360 --> 00:05:05.370 align:middle line:84%
And the reason why these
systems are more efficient

00:05:05.370 --> 00:05:07.630 align:middle line:84%
is because of this
sine graph here.

00:05:07.630 --> 00:05:10.920 align:middle line:84%
So the source temperature
is going to that heat pump

00:05:10.920 --> 00:05:12.480 align:middle line:84%
from the ground
heat exchanger range

00:05:12.480 --> 00:05:15.550 align:middle line:84%
between around 40 to
90 degrees Fahrenheit,

00:05:15.550 --> 00:05:17.410 align:middle line:90%
sometimes as low as 30.

00:05:17.410 --> 00:05:20.340 align:middle line:84%
But this specific
graph is collected

00:05:20.340 --> 00:05:23.430 align:middle line:84%
from four years' worth of
data in a very cold climate

00:05:23.430 --> 00:05:25.150 align:middle line:90%
in Winnipeg, Manitoba.

00:05:25.150 --> 00:05:28.680 align:middle line:84%
So during this same time period,
the outdoor air temperature

00:05:28.680 --> 00:05:33.160 align:middle line:84%
ranged from negative 20 to
plus 100 degrees Fahrenheit.

00:05:33.160 --> 00:05:35.880 align:middle line:84%
So you can imagine that getting
your source temperatures

00:05:35.880 --> 00:05:40.650 align:middle line:84%
from that more extreme air
compared to your ground heat

00:05:40.650 --> 00:05:43.770 align:middle line:84%
exchanger temperatures makes
the heat pump work harder.

00:05:43.770 --> 00:05:46.770 align:middle line:84%
It has to work harder to deliver
that same amount of heat.

00:05:46.770 --> 00:05:51.310 align:middle line:84%
So heat pumps like to receive
more moderate temperatures,

00:05:51.310 --> 00:05:52.900 align:middle line:84%
so they don't need
to work as hard.

00:05:52.900 --> 00:05:56.870 align:middle line:84%
And how a heat pump works
is just like a fridge.

00:05:56.870 --> 00:05:59.430 align:middle line:84%
It's the vapor compression
cycle is what it's called.

00:05:59.430 --> 00:06:02.040 align:middle line:84%
It's no different than a fridge,
other than a reversing valve.

00:06:02.040 --> 00:06:06.710 align:middle line:84%
But the process is you have an
evaporator that transfers heat

00:06:06.710 --> 00:06:10.070 align:middle line:84%
with your external environment,
so your air, your ground,

00:06:10.070 --> 00:06:11.160 align:middle line:90%
or your water.

00:06:11.160 --> 00:06:13.970 align:middle line:84%
You have a compressor, which
compresses the refrigerant

00:06:13.970 --> 00:06:16.110 align:middle line:84%
and increasing the
pressure and temperature.

00:06:16.110 --> 00:06:18.840 align:middle line:84%
Chemistry 101, if you
increase pressure,

00:06:18.840 --> 00:06:20.340 align:middle line:90%
you increase the temperature.

00:06:20.340 --> 00:06:23.540 align:middle line:84%
You have your condenser which
condenses the refrigerant vapor

00:06:23.540 --> 00:06:24.180 align:middle line:90%
into liquid.

00:06:24.180 --> 00:06:27.030 align:middle line:84%
And that phase change
transfers large amount of heat.

00:06:27.030 --> 00:06:30.020 align:middle line:84%
And then your expansion valve
to rinse and repeat, reduce

00:06:30.020 --> 00:06:32.820 align:middle line:84%
the pressure and temperature
to prepare for the next cycle.

00:06:32.820 --> 00:06:36.110 align:middle line:84%
So our ground-source
heat pump in heating,

00:06:36.110 --> 00:06:38.040 align:middle line:84%
again, we have this
reversing valve,

00:06:38.040 --> 00:06:41.220 align:middle line:84%
which differentiates our
fridge from our heat pump.

00:06:41.220 --> 00:06:42.690 align:middle line:90%
So we can also do heating.

00:06:42.690 --> 00:06:45.140 align:middle line:84%
Be strange if a
fridge did heating.

00:06:45.140 --> 00:06:48.080 align:middle line:84%
But we extract heat
from our ground loop,

00:06:48.080 --> 00:06:51.330 align:middle line:84%
where we have three units of
heat coming from the ground.

00:06:51.330 --> 00:06:54.110 align:middle line:84%
We have our compressor,
which uses electricity

00:06:54.110 --> 00:06:56.450 align:middle line:84%
to compress and heat
the refrigerant.

00:06:56.450 --> 00:06:58.720 align:middle line:84%
That electrically
powered equipment

00:06:58.720 --> 00:07:00.080 align:middle line:90%
generates heat as well.

00:07:00.080 --> 00:07:02.990 align:middle line:84%
That's your power
input, that compressor.

00:07:02.990 --> 00:07:05.240 align:middle line:84%
There's also the
circulation pump and fans.

00:07:05.240 --> 00:07:08.630 align:middle line:84%
And then you give those four
units of heat to the building.

00:07:08.630 --> 00:07:11.500 align:middle line:84%
So that hot refrigerant is
pushed through the condenser

00:07:11.500 --> 00:07:14.120 align:middle line:84%
and then rejects that heat
to the air in the building.

00:07:14.120 --> 00:07:16.670 align:middle line:84%
And this is how you get your
coefficient of performance.

00:07:16.670 --> 00:07:19.870 align:middle line:84%
So you may have heard the
word COP, or coefficient

00:07:19.870 --> 00:07:21.950 align:middle line:84%
of performance, and
this is how it works.

00:07:21.950 --> 00:07:24.920 align:middle line:84%
You transfer those
four units of energy,

00:07:24.920 --> 00:07:29.140 align:middle line:84%
which is combined thermal and
electrical energy to the space

00:07:29.140 --> 00:07:33.820 align:middle line:84%
by only paying for one unit
of electrical energy to power

00:07:33.820 --> 00:07:37.360 align:middle line:84%
that compressor,
circulation pump, and fans.

00:07:37.360 --> 00:07:40.600 align:middle line:84%
In cooling mode,
we have our heat

00:07:40.600 --> 00:07:42.980 align:middle line:84%
that's extracted from
the air in the building,

00:07:42.980 --> 00:07:44.780 align:middle line:90%
vaporizing the refrigerant.

00:07:44.780 --> 00:07:46.760 align:middle line:84%
So those three units of
heat from the building.

00:07:46.760 --> 00:07:51.140 align:middle line:84%
We have our compressor again
that compresses and heats

00:07:51.140 --> 00:07:53.540 align:middle line:84%
the refrigerant or
reversing valve is on.

00:07:53.540 --> 00:07:56.400 align:middle line:84%
So we flip that
flow of refrigerant.

00:07:56.400 --> 00:07:57.960 align:middle line:90%
So it's going in reverse now.

00:07:57.960 --> 00:08:01.430 align:middle line:84%
And then that hot refrigerant
is pushed through the condenser

00:08:01.430 --> 00:08:04.160 align:middle line:84%
and rejects heat to that
ground heat exchanger.

00:08:04.160 --> 00:08:07.910 align:middle line:84%
We need to get rid of that
electrical energy and electrical

00:08:07.910 --> 00:08:09.780 align:middle line:84%
heat and that heat
from the building.

00:08:09.780 --> 00:08:12.020 align:middle line:84%
And we put that in
the ground loop.

00:08:12.020 --> 00:08:16.010 align:middle line:84%
So what's the difference
between Earth energy resource

00:08:16.010 --> 00:08:18.200 align:middle line:84%
engineering or
geothermal engineering

00:08:18.200 --> 00:08:21.330 align:middle line:90%
and conventional HVAC systems?

00:08:21.330 --> 00:08:24.200 align:middle line:84%
Well, the main difference is
that for ground-source heat pump

00:08:24.200 --> 00:08:29.313 align:middle line:84%
systems, you should be
considering the total demand.

00:08:29.313 --> 00:08:30.980 align:middle line:84%
The total demand of
a building, not just

00:08:30.980 --> 00:08:32.843 align:middle line:84%
a peak of the coldest
day of the year

00:08:32.843 --> 00:08:34.760 align:middle line:84%
or the warmest day of
the year, but your total

00:08:34.760 --> 00:08:36.830 align:middle line:84%
heating and cooling
on an annual basis

00:08:36.830 --> 00:08:38.400 align:middle line:90%
to determine your total supply.

00:08:38.400 --> 00:08:40.466 align:middle line:84%
Because you're
designing your source.

00:08:40.466 --> 00:08:44.000 align:middle line:84%
And so in a
conventional system, you

00:08:44.000 --> 00:08:46.040 align:middle line:84%
have a pipeline
that's large enough

00:08:46.040 --> 00:08:50.400 align:middle line:84%
to meet the peak heating day,
the coldest day of the year.

00:08:50.400 --> 00:08:52.400 align:middle line:84%
You have your
natural gas pipeline

00:08:52.400 --> 00:08:54.390 align:middle line:90%
that's feeding that equipment.

00:08:54.390 --> 00:08:58.040 align:middle line:84%
You have your water
utility line that's

00:08:58.040 --> 00:09:00.260 align:middle line:84%
feeding your cooling
tower to dissipate heat

00:09:00.260 --> 00:09:02.130 align:middle line:90%
on the warmest day of the year.

00:09:02.130 --> 00:09:05.940 align:middle line:84%
And as long as you pay your
energy bill, you should be OK.

00:09:05.940 --> 00:09:09.810 align:middle line:84%
But for a ground-source
heat pump scenario,

00:09:09.810 --> 00:09:12.990 align:middle line:84%
we are also considered
with our total loads.

00:09:12.990 --> 00:09:15.480 align:middle line:84%
Again, because we're
designing our source.

00:09:15.480 --> 00:09:17.670 align:middle line:84%
So this example
illustrates this.

00:09:17.670 --> 00:09:19.820 align:middle line:84%
So we have a church,
a retail store,

00:09:19.820 --> 00:09:21.210 align:middle line:90%
and an apartment building.

00:09:21.210 --> 00:09:25.830 align:middle line:84%
They may have the exact same
peak heating and cooling loads,

00:09:25.830 --> 00:09:30.990 align:middle line:84%
40 tons of cooling and
385 MBH of heating.

00:09:30.990 --> 00:09:34.250 align:middle line:84%
But due to the difference
in occupancy of those three

00:09:34.250 --> 00:09:36.890 align:middle line:84%
different buildings, the total
heating and cooling loads

00:09:36.890 --> 00:09:38.780 align:middle line:84%
are going to change
quite dramatically.

00:09:38.780 --> 00:09:42.410 align:middle line:84%
You think about that church,
probably highly occupied

00:09:42.410 --> 00:09:43.632 align:middle line:90%
once or twice a week.

00:09:43.632 --> 00:09:45.840 align:middle line:84%
You have a lot of people in
the room like this space.

00:09:45.840 --> 00:09:47.130 align:middle line:90%
You have a lot of lights on.

00:09:47.130 --> 00:09:51.630 align:middle line:84%
Those internal heat gains
help heat the space,

00:09:51.630 --> 00:09:55.000 align:middle line:84%
and that's only available
maybe once or twice a week.

00:09:55.000 --> 00:10:00.870 align:middle line:84%
So your heating load over
an annual set of data

00:10:00.870 --> 00:10:03.880 align:middle line:84%
is probably going to be
higher than your cooling load.

00:10:03.880 --> 00:10:07.420 align:middle line:84%
Whereas your retail store, you
could think of maybe an IKEA,

00:10:07.420 --> 00:10:09.760 align:middle line:84%
you have a lot of internal
heat gains, a lot of people,

00:10:09.760 --> 00:10:12.913 align:middle line:84%
a lot of lights, a lot
of internal heat gains

00:10:12.913 --> 00:10:14.080 align:middle line:90%
that you need to get rid of.

00:10:14.080 --> 00:10:15.730 align:middle line:84%
So you put those in
the ground, right?

00:10:15.730 --> 00:10:17.680 align:middle line:90%
You need to reject that heat.

00:10:17.680 --> 00:10:20.970 align:middle line:84%
And the apartment building
probably relatively balanced

00:10:20.970 --> 00:10:22.390 align:middle line:90%
between heating and cooling.

00:10:22.390 --> 00:10:24.690 align:middle line:84%
So the heating and
cooling load ratio

00:10:24.690 --> 00:10:27.900 align:middle line:84%
can change even if the peak
heating and cooling loads

00:10:27.900 --> 00:10:29.080 align:middle line:90%
are the exact same.

00:10:29.080 --> 00:10:31.560 align:middle line:84%
And how this affects
the ground loop and why

00:10:31.560 --> 00:10:33.430 align:middle line:90%
it's important is because--

00:10:33.430 --> 00:10:36.510 align:middle line:84%
and this is especially true for
a vertical ground heat exchanger

00:10:36.510 --> 00:10:38.670 align:middle line:84%
scenario with a
lot of conduction--

00:10:38.670 --> 00:10:41.130 align:middle line:84%
you have a fixed volume
of Earth that you're

00:10:41.130 --> 00:10:42.550 align:middle line:90%
exchanging heat with.

00:10:42.550 --> 00:10:46.380 align:middle line:84%
And so it's more similar to a
battery in that case compared

00:10:46.380 --> 00:10:47.620 align:middle line:90%
to a conventional system.

00:10:47.620 --> 00:10:48.970 align:middle line:90%
There are nuances, right.

00:10:48.970 --> 00:10:52.760 align:middle line:90%
And each project is unique.

00:10:52.760 --> 00:10:56.010 align:middle line:84%
But even in open loop
systems, for example,

00:10:56.010 --> 00:10:57.710 align:middle line:84%
where you're tapping
into an aquifer

00:10:57.710 --> 00:11:01.460 align:middle line:84%
and pulling heat and
rejecting heat to an aquifer,

00:11:01.460 --> 00:11:06.500 align:middle line:84%
we've been measuring a system
in Winnipeg over the past five

00:11:06.500 --> 00:11:08.060 align:middle line:84%
years or so, and
they've increased

00:11:08.060 --> 00:11:12.380 align:middle line:84%
the temperature of that aquifer
by 5 to 8 degrees Fahrenheit.

00:11:12.380 --> 00:11:15.330 align:middle line:84%
Just because they're rejecting
so much heat into that aquifer.

00:11:15.330 --> 00:11:17.100 align:middle line:84%
So what can happen
is this curve here,

00:11:17.100 --> 00:11:19.070 align:middle line:84%
this temperature
drift, where you

00:11:19.070 --> 00:11:22.260 align:middle line:84%
may fall outside of those
efficient operating parameters.

00:11:22.260 --> 00:11:24.410 align:middle line:84%
When we talked about that
ground-source heat pump,

00:11:24.410 --> 00:11:28.160 align:middle line:84%
it likes to be fed 30 to 90
degrees Fahrenheit water.

00:11:28.160 --> 00:11:31.670 align:middle line:84%
But what can happen is
you can fall outside

00:11:31.670 --> 00:11:33.890 align:middle line:84%
of those efficient
operating ranges

00:11:33.890 --> 00:11:36.410 align:middle line:84%
if you're not considering
your total loads,

00:11:36.410 --> 00:11:38.160 align:middle line:84%
if you're only looking
at your peak loads.

00:11:38.160 --> 00:11:42.888 align:middle line:84%
So it's important to not only
design, again, off of your peak

00:11:42.888 --> 00:11:44.430 align:middle line:84%
loads, which are
certainly important,

00:11:44.430 --> 00:11:47.480 align:middle line:84%
but your total loads are
also important to determine

00:11:47.480 --> 00:11:52.360 align:middle line:84%
your total demand to
design your supply.

00:11:52.360 --> 00:11:56.810 align:middle line:84%
So when you have a customer
or anyone, frankly,

00:11:56.810 --> 00:12:00.020 align:middle line:84%
who's interested in a geothermal
system, where do you start?

00:12:00.020 --> 00:12:03.280 align:middle line:84%
If they say, hey
Connor, I've heard

00:12:03.280 --> 00:12:05.060 align:middle line:90%
of this geothermal technology.

00:12:05.060 --> 00:12:06.760 align:middle line:90%
I've heard it's pretty cool.

00:12:06.760 --> 00:12:07.880 align:middle line:90%
What do I do?

00:12:07.880 --> 00:12:11.020 align:middle line:84%
Well, you'd probably want
to start with the building.

00:12:11.020 --> 00:12:14.660 align:middle line:84%
Again, determine your total
demand to determine your supply.

00:12:14.660 --> 00:12:17.300 align:middle line:84%
And then you can start looking
at your mechanical system,

00:12:17.300 --> 00:12:19.420 align:middle line:84%
your geothermal mechanical
system, and your site

00:12:19.420 --> 00:12:20.252 align:middle line:90%
and geology.

00:12:20.252 --> 00:12:22.960 align:middle line:84%
The site and geology is going to
dictate what type of ground heat

00:12:22.960 --> 00:12:24.140 align:middle line:90%
exchanger you go with.

00:12:24.140 --> 00:12:26.050 align:middle line:84%
There's many different
ways to exchange heat

00:12:26.050 --> 00:12:27.710 align:middle line:90%
with your external environment.

00:12:27.710 --> 00:12:31.573 align:middle line:84%
Again, all you're doing is
obtaining moderate temperatures

00:12:31.573 --> 00:12:33.740 align:middle line:84%
so that your heat pump
doesn't need to work as hard.

00:12:33.740 --> 00:12:35.360 align:middle line:90%
So that could come from the air.

00:12:35.360 --> 00:12:38.390 align:middle line:84%
In Seattle, it's
pretty moderate there.

00:12:38.390 --> 00:12:40.000 align:middle line:90%
So air source works fine.

00:12:40.000 --> 00:12:43.370 align:middle line:84%
But in Winnipeg in a cold
climate like that, not so much.

00:12:43.370 --> 00:12:45.400 align:middle line:84%
So you could have a
vertical ground heat

00:12:45.400 --> 00:12:48.560 align:middle line:84%
exchanger, horizontal
surface water aquifer.

00:12:48.560 --> 00:12:51.660 align:middle line:84%
I'm staying at Susan
Murcott's house right now.

00:12:51.660 --> 00:12:54.635 align:middle line:84%
She's a professor here at MIT,
and she has a standing column.

00:12:54.635 --> 00:12:56.260 align:middle line:84%
And that was pretty
interesting to see.

00:12:56.260 --> 00:13:00.120 align:middle line:84%
So there's many different ways
to give your heat pump source

00:13:00.120 --> 00:13:01.860 align:middle line:90%
temperatures that are moderate.

00:13:01.860 --> 00:13:04.200 align:middle line:84%
But at the end of the
day, what matters?

00:13:04.200 --> 00:13:07.410 align:middle line:84%
Well, what matters is we're
trying to save on energy.

00:13:07.410 --> 00:13:09.220 align:middle line:84%
That's why we install
these systems.

00:13:09.220 --> 00:13:11.842 align:middle line:84%
But if it's going to cost you
an arm and a leg to do that,

00:13:11.842 --> 00:13:14.050 align:middle line:84%
it's probably not going to
make a whole lot of sense.

00:13:14.050 --> 00:13:17.490 align:middle line:84%
So to balance the energy cost
with the construction cost

00:13:17.490 --> 00:13:20.890 align:middle line:84%
is the most important thing to
make sure that it's practical.

00:13:20.890 --> 00:13:23.730 align:middle line:84%
Because if it's too
expensive, nobody's

00:13:23.730 --> 00:13:26.610 align:middle line:84%
going to buy it at
the end of the day.

00:13:26.610 --> 00:13:27.900 align:middle line:90%
And there are intangibles.

00:13:27.900 --> 00:13:30.730 align:middle line:84%
A lot of people value
carbon in different ways.

00:13:30.730 --> 00:13:32.910 align:middle line:90%
In Canada, we have a carbon tax.

00:13:32.910 --> 00:13:35.730 align:middle line:90%
So that's quantified.

00:13:35.730 --> 00:13:38.640 align:middle line:84%
But the main thing
to consider when

00:13:38.640 --> 00:13:41.110 align:middle line:84%
you're looking at a geothermal
system, in my opinion,

00:13:41.110 --> 00:13:43.680 align:middle line:84%
is to balance these two things--
construction cost and then

00:13:43.680 --> 00:13:46.410 align:middle line:84%
the energy savings that you're
getting from that investment,

00:13:46.410 --> 00:13:49.170 align:middle line:84%
because you're buying an asset,
which is that ground heat

00:13:49.170 --> 00:13:51.050 align:middle line:90%
exchanger.

00:13:51.050 --> 00:13:53.490 align:middle line:84%
So before I pass it
to my colleague Nick,

00:13:53.490 --> 00:13:56.430 align:middle line:84%
I thought I'd throw in a
little segue slide here.

00:13:56.430 --> 00:14:00.590 align:middle line:84%
I believe one person had
a similar slide yesterday

00:14:00.590 --> 00:14:03.230 align:middle line:84%
where it looks at the
temperature in the distribution

00:14:03.230 --> 00:14:06.900 align:middle line:90%
piping of district systems.

00:14:06.900 --> 00:14:08.760 align:middle line:84%
We used to use really
high temperature.

00:14:08.760 --> 00:14:11.340 align:middle line:84%
I mean, we still do
today, pressurized steam,

00:14:11.340 --> 00:14:13.410 align:middle line:84%
but that leads to
low efficiency.

00:14:13.410 --> 00:14:16.760 align:middle line:84%
And so over time, we've been
able to reduce our temperature

00:14:16.760 --> 00:14:19.460 align:middle line:84%
in our distribution
piping, which has led

00:14:19.460 --> 00:14:20.940 align:middle line:90%
to an increase in efficiency.

00:14:20.940 --> 00:14:23.420 align:middle line:84%
So now we're dealing with
ambient temperatures, which

00:14:23.420 --> 00:14:26.450 align:middle line:84%
has increased our efficiency in
these district energy systems

00:14:26.450 --> 00:14:27.330 align:middle line:90%
quite dramatically.

00:14:27.330 --> 00:14:28.950 align:middle line:84%
So thank you folks
for listening,

00:14:28.950 --> 00:14:31.092 align:middle line:90%
and I'll now pass it to Nick.

00:14:31.092 --> 00:14:35.520 align:middle line:90%
[APPLAUSE]

00:14:35.520 --> 00:14:37.490 align:middle line:90%


00:14:37.490 --> 00:14:38.920 align:middle line:90%
OK.