PROFESSOR: And so
next we have Susan.

00:00:18.010 --> 00:00:21.720 align:middle line:90%


00:00:21.720 --> 00:00:22.780 align:middle line:90%
You need the clicker?

00:00:22.780 --> 00:00:24.440 align:middle line:84%
SUSAN MURCOTT: I do
need the clicker.

00:00:24.440 --> 00:00:26.200 align:middle line:90%
I don't need this.

00:00:26.200 --> 00:00:28.260 align:middle line:84%
PROFESSOR: It's about
the MIT project.

00:00:28.260 --> 00:00:30.720 align:middle line:84%
SUSAN MURCOTT: Wow,
that was fantastic.

00:00:30.720 --> 00:00:35.640 align:middle line:84%
I also want to add my voice
to this chorus, my voice

00:00:35.640 --> 00:00:38.320 align:middle line:84%
and my colleagues'
voice, and to start

00:00:38.320 --> 00:00:41.520 align:middle line:84%
by thanking Zeyneb and this
incredible group that's

00:00:41.520 --> 00:00:42.840 align:middle line:90%
joined here today.

00:00:42.840 --> 00:00:46.240 align:middle line:84%
And to say that you
all are pioneers.

00:00:46.240 --> 00:00:50.120 align:middle line:84%
I've been so moved by
so much creative work

00:00:50.120 --> 00:00:53.320 align:middle line:84%
by so many leaders in the field
that have been brought together.

00:00:53.320 --> 00:00:55.960 align:middle line:90%
It's truly remarkable.

00:00:55.960 --> 00:00:58.040 align:middle line:90%
And so thank you.

00:00:58.040 --> 00:01:02.310 align:middle line:84%
I'm going to introduce to
you the MIT Thermal Energy

00:01:02.310 --> 00:01:06.390 align:middle line:84%
Network, or MITTEN, plan
for rapid, cost-effective

00:01:06.390 --> 00:01:09.350 align:middle line:90%
decarbonization at MIT campus.

00:01:09.350 --> 00:01:13.550 align:middle line:84%
It is the work of
MACA MIT campus group.

00:01:13.550 --> 00:01:17.990 align:middle line:84%
MACA stands for MIT
Alumni for Climate Action,

00:01:17.990 --> 00:01:21.210 align:middle line:84%
in collaboration
with Geo at MIT,

00:01:21.210 --> 00:01:23.990 align:middle line:84%
which is the student group
that we've worked with.

00:01:23.990 --> 00:01:26.750 align:middle line:90%
MACA was founded in 2018.

00:01:26.750 --> 00:01:31.790 align:middle line:84%
The idea for a thermal
energy network for MIT campus

00:01:31.790 --> 00:01:34.430 align:middle line:84%
goes to Rick
Clemenzi a colleague

00:01:34.430 --> 00:01:40.230 align:middle line:84%
of Garen Ewbank, who
we heard from earlier.

00:01:40.230 --> 00:01:44.750 align:middle line:84%
Rick and Judy won a
Climate CoLab competition

00:01:44.750 --> 00:01:47.750 align:middle line:90%
that MIT sponsored in 2016.

00:01:47.750 --> 00:01:49.130 align:middle line:90%
But it didn't go anywhere.

00:01:49.130 --> 00:01:53.630 align:middle line:84%
MIT wasn't interested at the
time in listening to that.

00:01:53.630 --> 00:01:56.030 align:middle line:90%
We picked that up at MIT--

00:01:56.030 --> 00:01:58.270 align:middle line:84%
the MACA group
picked up that idea

00:01:58.270 --> 00:02:00.830 align:middle line:84%
and have built on it for
the past three years,

00:02:00.830 --> 00:02:03.390 align:middle line:84%
and we just
introduced it formally

00:02:03.390 --> 00:02:08.460 align:middle line:84%
in a class that I
taught this past week,

00:02:08.460 --> 00:02:11.700 align:middle line:84%
and in an hour-long
presentation, which

00:02:11.700 --> 00:02:14.060 align:middle line:84%
has been reduced to
10 minutes for today.

00:02:14.060 --> 00:02:17.300 align:middle line:84%
So moving along, MIT's
decarbonization challenge

00:02:17.300 --> 00:02:21.140 align:middle line:84%
is that 97% of MIT's
greenhouse gas emissions

00:02:21.140 --> 00:02:23.300 align:middle line:84%
are from the operation
of its buildings.

00:02:23.300 --> 00:02:27.530 align:middle line:84%
And 26% of all of Cambridge's
greenhouse gases are from MIT.

00:02:27.530 --> 00:02:30.220 align:middle line:90%


00:02:30.220 --> 00:02:35.140 align:middle line:84%
MIT has had two climate
action plans in 2016 and 2021,

00:02:35.140 --> 00:02:38.500 align:middle line:84%
which postponed significant
investment in direct campus

00:02:38.500 --> 00:02:41.500 align:middle line:90%
decarbonization until later.

00:02:41.500 --> 00:02:46.180 align:middle line:84%
Its emphasis in the early years,
2020 up to 2040 and going on,

00:02:46.180 --> 00:02:52.460 align:middle line:84%
is a power purchase agreements
in the Midwest, and mainly

00:02:52.460 --> 00:02:54.540 align:middle line:90%
the power purchase agreements.

00:02:54.540 --> 00:03:00.500 align:middle line:84%
But it hopes for some major
breakthroughs in the future.

00:03:00.500 --> 00:03:02.500 align:middle line:90%
And is going to--

00:03:02.500 --> 00:03:06.570 align:middle line:84%
there are voices among
this chorus at MIT

00:03:06.570 --> 00:03:11.050 align:middle line:84%
who would like to see
small nuclear reactors

00:03:11.050 --> 00:03:14.290 align:middle line:84%
or deep geothermal at
some future point when

00:03:14.290 --> 00:03:17.810 align:middle line:90%
it becomes a reality.

00:03:17.810 --> 00:03:21.410 align:middle line:84%
The MIT thermal energy
decarbonization plan

00:03:21.410 --> 00:03:25.370 align:middle line:84%
is an all-electric campus
fueled by carbon-free power.

00:03:25.370 --> 00:03:27.870 align:middle line:84%
It implements energy
conservation measures,

00:03:27.870 --> 00:03:31.130 align:middle line:84%
including waste heat recovery
from ventilation systems

00:03:31.130 --> 00:03:33.010 align:middle line:90%
to reduce heating and cooling.

00:03:33.010 --> 00:03:35.210 align:middle line:84%
We're installing high-efficiency
water source heat

00:03:35.210 --> 00:03:39.850 align:middle line:84%
pumps in each
building distributed

00:03:39.850 --> 00:03:41.610 align:middle line:90%
for heating and cooling.

00:03:41.610 --> 00:03:46.290 align:middle line:84%
It repurposes the existing
chiller loop to an ambient loop,

00:03:46.290 --> 00:03:50.530 align:middle line:84%
circulating 45 to 85-degree
water year round to water source

00:03:50.530 --> 00:03:52.210 align:middle line:90%
heat pumps in each building.

00:03:52.210 --> 00:03:56.250 align:middle line:84%
It repurposes the oil tanks
at the CUP, Central Utilities

00:03:56.250 --> 00:03:58.410 align:middle line:90%
Plant, for thermal storage.

00:03:58.410 --> 00:04:00.290 align:middle line:84%
And there are energy
transfer stations

00:04:00.290 --> 00:04:03.030 align:middle line:84%
operated by the Cambridge
Water Department,

00:04:03.030 --> 00:04:06.650 align:middle line:84%
exchanging heat with the
ambient loop where possible.

00:04:06.650 --> 00:04:11.590 align:middle line:84%
And if not, then looking to the
MWRA and the wastewater sewage

00:04:11.590 --> 00:04:15.590 align:middle line:84%
or drilling
geothermal boreholes.

00:04:15.590 --> 00:04:17.550 align:middle line:84%
The plan is the most
cost-effective and

00:04:17.550 --> 00:04:21.790 align:middle line:84%
energy-efficient way to
decarbonize the campus.

00:04:21.790 --> 00:04:23.870 align:middle line:90%
It demonstrates MIT leadership.

00:04:23.870 --> 00:04:27.870 align:middle line:84%
It leverages MIT's investment
in existing infrastructure.

00:04:27.870 --> 00:04:31.990 align:middle line:84%
It eliminates the cost impact
of maintaining separate systems

00:04:31.990 --> 00:04:35.950 align:middle line:84%
because the water source heat
pumps provide both heating

00:04:35.950 --> 00:04:37.350 align:middle line:90%
and cooling.

00:04:37.350 --> 00:04:40.270 align:middle line:84%
It eliminates energy
transmission losses,

00:04:40.270 --> 00:04:42.550 align:middle line:84%
enables the capture
of free energy

00:04:42.550 --> 00:04:45.430 align:middle line:84%
where there is concurrent
heating and cooling on campus,

00:04:45.430 --> 00:04:50.110 align:middle line:84%
and perhaps will tap
into future subsidies.

00:04:50.110 --> 00:04:53.190 align:middle line:84%
The Met building already
demonstrates this,

00:04:53.190 --> 00:04:57.630 align:middle line:84%
and that demonstration
is underway.

00:04:57.630 --> 00:04:59.450 align:middle line:84%
How is the campus
heated and cooled now?

00:04:59.450 --> 00:05:02.670 align:middle line:84%
It has a central utilities
plant with cogeneration.

00:05:02.670 --> 00:05:05.030 align:middle line:90%
It produces steam and hot water.

00:05:05.030 --> 00:05:07.710 align:middle line:84%
It operates on a
steam-driven chiller.

00:05:07.710 --> 00:05:11.540 align:middle line:84%
It generates over 22 megawatts
of electric power connected

00:05:11.540 --> 00:05:15.060 align:middle line:84%
to steam distribution,
connected to chilled water

00:05:15.060 --> 00:05:17.380 align:middle line:90%
distribution to most buildings.

00:05:17.380 --> 00:05:22.660 align:middle line:84%
And the cooling load is high and
most affected by global warming.

00:05:22.660 --> 00:05:26.060 align:middle line:84%
Decarbonization issues
with the existing plant,

00:05:26.060 --> 00:05:30.380 align:middle line:84%
the grid decarbonization
is rapidly reducing carbon,

00:05:30.380 --> 00:05:33.940 align:middle line:84%
once touted for a
combined heat and power.

00:05:33.940 --> 00:05:36.500 align:middle line:90%
Fossil fuel backup is necessary.

00:05:36.500 --> 00:05:40.340 align:middle line:84%
Efficiency of 50% to
55% source to output.

00:05:40.340 --> 00:05:43.020 align:middle line:90%
Low turndown rate of about 30%.

00:05:43.020 --> 00:05:45.820 align:middle line:84%
High thermal losses in the
steam distribution system

00:05:45.820 --> 00:05:47.700 align:middle line:90%
of 10% to 20%.

00:05:47.700 --> 00:05:52.500 align:middle line:84%
Nonzero losses in the chilled
water system of 5% to 15%.

00:05:52.500 --> 00:05:57.260 align:middle line:84%
And also the hot water district
system have losses also.

00:05:57.260 --> 00:06:02.020 align:middle line:84%
And hot water is what MIT's
administration is currently

00:06:02.020 --> 00:06:09.240 align:middle line:84%
seeming to embrace for its
favored geothermal pathway

00:06:09.240 --> 00:06:11.210 align:middle line:90%
option.

00:06:11.210 --> 00:06:15.050 align:middle line:84%
How would the MITTEN plan
heat and cool the campus?

00:06:15.050 --> 00:06:17.210 align:middle line:84%
Distributed heat pumps
connected to a network

00:06:17.210 --> 00:06:18.930 align:middle line:90%
of sources and sinks.

00:06:18.930 --> 00:06:21.130 align:middle line:84%
No one solution, since
the buildings range

00:06:21.130 --> 00:06:23.650 align:middle line:90%
over a history of 100 years.

00:06:23.650 --> 00:06:26.930 align:middle line:84%
Use of building-to-building and
building-in-building sources

00:06:26.930 --> 00:06:28.370 align:middle line:90%
and sinks.

00:06:28.370 --> 00:06:31.770 align:middle line:84%
Use of thermal energy
storage and ground coupling

00:06:31.770 --> 00:06:34.450 align:middle line:84%
with, as I've said,
Cambridge Water, sewer,

00:06:34.450 --> 00:06:38.290 align:middle line:90%
or ground thermal exchanges.

00:06:38.290 --> 00:06:41.850 align:middle line:84%
We consider this a fifth or
sixth generation district HVAC

00:06:41.850 --> 00:06:45.690 align:middle line:84%
decarbonization transition
with an ambient loop,

00:06:45.690 --> 00:06:49.050 align:middle line:84%
two-pipe system, exhaust
recovery, distributed water

00:06:49.050 --> 00:06:52.190 align:middle line:84%
source heat pumps, thermal
storage, air source heat pumps,

00:06:52.190 --> 00:06:55.050 align:middle line:84%
and ground heat exchange,
municipal water thermal,

00:06:55.050 --> 00:06:57.305 align:middle line:90%
and other.

00:06:57.305 --> 00:07:02.730 align:middle line:84%
And the chiller loop to the
ambient loop conversion,

00:07:02.730 --> 00:07:08.090 align:middle line:84%
we would use the same two
pipes that exist already.

00:07:08.090 --> 00:07:14.520 align:middle line:84%
First of all, the blue buildings
have currently chiller loop.

00:07:14.520 --> 00:07:17.160 align:middle line:90%
Oh, and I didn't say we have--

00:07:17.160 --> 00:07:21.640 align:middle line:84%
MIT administration provided
us with a memorandum

00:07:21.640 --> 00:07:27.280 align:middle line:84%
of understanding to test fit
our idea to six buildings.

00:07:27.280 --> 00:07:31.240 align:middle line:84%
And those six
buildings are here.

00:07:31.240 --> 00:07:34.440 align:middle line:84%
W20 is the Student
Center, and the rest

00:07:34.440 --> 00:07:38.680 align:middle line:84%
are the athletic
complex, W31 to W35.

00:07:38.680 --> 00:07:41.080 align:middle line:84%
And three of those
buildings have--

00:07:41.080 --> 00:07:44.280 align:middle line:84%
the blue buildings--
have the chiller loop,

00:07:44.280 --> 00:07:45.900 align:middle line:90%
but the other three do not.

00:07:45.900 --> 00:07:47.840 align:middle line:90%
So our plan would--

00:07:47.840 --> 00:07:50.880 align:middle line:84%
for the test fit, would
require the chiller loop

00:07:50.880 --> 00:07:52.480 align:middle line:90%
to be added to these three--

00:07:52.480 --> 00:07:52.980 align:middle line:90%
excuse me.

00:07:52.980 --> 00:07:55.800 align:middle line:84%
The ambient loop to be added
to these three buildings,

00:07:55.800 --> 00:07:58.120 align:middle line:84%
as represented by
the green dots.

00:07:58.120 --> 00:08:02.920 align:middle line:84%
Were our proposal for
these buildings expanded

00:08:02.920 --> 00:08:08.440 align:middle line:84%
to the whole campus, we would
also need an ambient loop here.

00:08:08.440 --> 00:08:12.760 align:middle line:84%
Those were the only two places
that we would need to do work.

00:08:12.760 --> 00:08:15.750 align:middle line:84%
And I meant to say
that here are the six

00:08:15.750 --> 00:08:20.930 align:middle line:84%
buildings on a graph of the EUIs
of a number of the buildings--

00:08:20.930 --> 00:08:23.070 align:middle line:84%
not all the buildings,
but most of the buildings.

00:08:23.070 --> 00:08:29.710 align:middle line:84%
And MIT has very high EUIs
with the lab buildings being--

00:08:29.710 --> 00:08:39.270 align:middle line:84%
ah, backwards-- the worst
performing buildings.

00:08:39.270 --> 00:08:42.150 align:middle line:84%
And what's interesting is
that these six buildings

00:08:42.150 --> 00:08:52.070 align:middle line:84%
represent quite a huge span
of the campus current EUIs.

00:08:52.070 --> 00:09:00.310 align:middle line:84%
So this is where in W33
the ambient loop would run.

00:09:00.310 --> 00:09:05.830 align:middle line:84%
And this is the
cluster from above

00:09:05.830 --> 00:09:09.270 align:middle line:84%
on which the ambient
loop that you just saw

00:09:09.270 --> 00:09:15.820 align:middle line:84%
would be running from
the chilled water loop

00:09:15.820 --> 00:09:21.380 align:middle line:84%
connection through what you just
saw, and through this building

00:09:21.380 --> 00:09:24.220 align:middle line:84%
and into this building
and also into W20.

00:09:24.220 --> 00:09:27.020 align:middle line:84%
We would also put
solar collectors

00:09:27.020 --> 00:09:32.580 align:middle line:84%
on these wonderful flat roofs
that are hidden from view.

00:09:32.580 --> 00:09:39.460 align:middle line:84%
And we would put on the roof
of W20, the Student Center,

00:09:39.460 --> 00:09:44.140 align:middle line:84%
multistack heat pump units where
there's already space for that.

00:09:44.140 --> 00:09:50.060 align:middle line:84%
We would put, as one option,
multistacks in W34 as well.

00:09:50.060 --> 00:09:56.940 align:middle line:84%
Perhaps another option would
be the AAON SA-23 in W34.

00:09:56.940 --> 00:10:02.460 align:middle line:84%
And then to compare, a central
plant four-pipe distribution

00:10:02.460 --> 00:10:05.140 align:middle line:84%
system, as is
being proposed, you

00:10:05.140 --> 00:10:11.660 align:middle line:84%
can see that MIT currently
has installed hot water

00:10:11.660 --> 00:10:13.820 align:middle line:90%
pipes in the Sloan complex.

00:10:13.820 --> 00:10:17.380 align:middle line:84%
It represents about
15% of the campus.

00:10:17.380 --> 00:10:22.730 align:middle line:84%
And the consultant's plan
would require hot water pipes

00:10:22.730 --> 00:10:26.370 align:middle line:90%
with, I believe, 180 to--

00:10:26.370 --> 00:10:31.650 align:middle line:84%
they call it low-temperature
pipes, but not so low--

00:10:31.650 --> 00:10:37.250 align:middle line:84%
180 to 240, I believe,
degrees Fahrenheit hot water

00:10:37.250 --> 00:10:38.570 align:middle line:90%
in these pipes.

00:10:38.570 --> 00:10:42.470 align:middle line:84%
And all of this would
need to be installed.

00:10:42.470 --> 00:10:45.810 align:middle line:84%
And of course, that
would need steel pipes

00:10:45.810 --> 00:10:52.540 align:middle line:84%
and insulated pipes as opposed
to the ambient loop small areas

00:10:52.540 --> 00:10:53.040 align:middle line:90%
here.

00:10:53.040 --> 00:10:55.690 align:middle line:90%


00:10:55.690 --> 00:11:02.890 align:middle line:84%
The central thermal plant has
heat losses in transmission.

00:11:02.890 --> 00:11:12.250 align:middle line:84%
It starts off with a lower COP
and MITTEN's has limited heat

00:11:12.250 --> 00:11:16.700 align:middle line:84%
losses because of each heat pump
being in the building itself.

00:11:16.700 --> 00:11:19.890 align:middle line:90%


00:11:19.890 --> 00:11:20.390 align:middle line:90%
So

00:11:20.390 --> 00:11:24.750 align:middle line:84%
To sum up a kind of top line
comparison of approaches.

00:11:24.750 --> 00:11:27.370 align:middle line:84%
Both approaches meet
building HVAC specs.

00:11:27.370 --> 00:11:30.830 align:middle line:84%
Both approaches
achieve zero emissions.

00:11:30.830 --> 00:11:34.670 align:middle line:84%
Our approach achieves
those emissions by 2035

00:11:34.670 --> 00:11:39.030 align:middle line:84%
were we to start this year
with a pilot on the existing

00:11:39.030 --> 00:11:42.190 align:middle line:90%
six-building complex.

00:11:42.190 --> 00:11:44.350 align:middle line:84%
Ours is minimally
disruptive, as you

00:11:44.350 --> 00:11:46.630 align:middle line:84%
saw, with the ambient
loop only needing

00:11:46.630 --> 00:11:49.990 align:middle line:90%
to be extended in a few places.

00:11:49.990 --> 00:11:52.430 align:middle line:84%
We need a pilot to
confirm our projections

00:11:52.430 --> 00:11:57.310 align:middle line:84%
and to learn, as the heat
Eversource demonstration has

00:11:57.310 --> 00:11:59.130 align:middle line:90%
learned, a tremendous amount.

00:11:59.130 --> 00:12:01.590 align:middle line:84%
We need to do that
learning on the MIT campus

00:12:01.590 --> 00:12:03.110 align:middle line:90%
by a real project.

00:12:03.110 --> 00:12:05.090 align:middle line:90%
It's easy to upgrade over time.

00:12:05.090 --> 00:12:06.750 align:middle line:90%
It's fiscally responsible.

00:12:06.750 --> 00:12:09.350 align:middle line:84%
And it's unclear whether
MIT will seriously

00:12:09.350 --> 00:12:13.390 align:middle line:90%
consider our proposal.

00:12:13.390 --> 00:12:18.230 align:middle line:84%
Our proposal we call a
thermal transition leapfrog.

00:12:18.230 --> 00:12:22.700 align:middle line:84%
And would go from the existing
chiller plant to a distributed

00:12:22.700 --> 00:12:24.700 align:middle line:90%
energy network.

00:12:24.700 --> 00:12:26.640 align:middle line:84%
So finally, at the
end of the day,

00:12:26.640 --> 00:12:29.040 align:middle line:84%
the project is not just
about public relations,

00:12:29.040 --> 00:12:31.340 align:middle line:84%
but it should result
in real progress.

00:12:31.340 --> 00:12:34.340 align:middle line:84%
The central utility plant
will play an important role

00:12:34.340 --> 00:12:36.220 align:middle line:90%
in the MITTEN solution.

00:12:36.220 --> 00:12:38.100 align:middle line:90%
Our plan is available now.

00:12:38.100 --> 00:12:40.100 align:middle line:84%
We're using
off-the-shelf equipment.

00:12:40.100 --> 00:12:41.400 align:middle line:90%
It's cost effective.

00:12:41.400 --> 00:12:43.580 align:middle line:84%
It will eliminate
carbon emissions

00:12:43.580 --> 00:12:45.700 align:middle line:90%
and be minimally disruptive.

00:12:45.700 --> 00:12:47.700 align:middle line:84%
We feel that we
can show the world

00:12:47.700 --> 00:12:49.960 align:middle line:84%
and demonstrate
to other campuses,

00:12:49.960 --> 00:12:53.620 align:middle line:84%
not only in Boston area
or across North America,

00:12:53.620 --> 00:12:55.660 align:middle line:84%
but around the
world, that this is

00:12:55.660 --> 00:13:01.220 align:middle line:84%
an approach that is cost
effective, rapid, and doable.

00:13:01.220 --> 00:13:04.260 align:middle line:84%
MIT's the world's leading
research institute

00:13:04.260 --> 00:13:07.700 align:middle line:84%
and should do something
that's not just a cookie

00:13:07.700 --> 00:13:12.300 align:middle line:84%
cutter that other campuses
have already done,

00:13:12.300 --> 00:13:16.340 align:middle line:84%
like Princeton or
like Stanford, and it

00:13:16.340 --> 00:13:18.660 align:middle line:90%
is a centralized approach.

00:13:18.660 --> 00:13:25.690 align:middle line:84%
And we need to do a pilot and
advocate for that for 2025

00:13:25.690 --> 00:13:30.530 align:middle line:84%
so that we can get
to net zero by 2035.

00:13:30.530 --> 00:13:32.970 align:middle line:84%
And I'll close with
words of Sally Kornbluth

00:13:32.970 --> 00:13:34.390 align:middle line:90%
at her inauguration.

00:13:34.390 --> 00:13:36.810 align:middle line:84%
Climate change and its
mounting consequence

00:13:36.810 --> 00:13:39.330 align:middle line:84%
is the greatest scientific
and societal challenge

00:13:39.330 --> 00:13:40.970 align:middle line:90%
of this or any age.

00:13:40.970 --> 00:13:44.210 align:middle line:84%
We need energy and expertise
from every MIT school

00:13:44.210 --> 00:13:47.130 align:middle line:84%
and college, and from
every lab and every center,

00:13:47.130 --> 00:13:49.010 align:middle line:84%
from every member
of the faculty,

00:13:49.010 --> 00:13:51.490 align:middle line:90%
and from every one of you.

00:13:51.490 --> 00:13:53.410 align:middle line:90%
So thank you.

00:13:53.410 --> 00:13:57.770 align:middle line:84%
And I think I want to end
really with this slide.

00:13:57.770 --> 00:14:00.290 align:middle line:90%
We want to get there by 2035.

00:14:00.290 --> 00:14:03.330 align:middle line:84%
And we're asking MIT,
when can we start?

00:14:03.330 --> 00:14:06.680 align:middle line:90%